Application of high voltage inverter in the transformation of induced draft fan

Application of high voltage inverter in the transformation of induced draft fan


Content abstract:According to the motor capacity of induced draft fan, the inverter hivert-y06 / 220 is selected, and the rated output current is 220a.The control power supply of frequency converter is controlled by 380V. One way of power supply is from the transformer of frequency converter, and the other way is from the 380V system of unit. The two ways of power supply can be automatically switched without manual adjustment.

key word:Energy saving inverter hydraulic coupler

1、 Current situation of induced draft fan before transformation

The self provided power plant is a 3 × 135wm circulating vulcanization bed generator set.All six induced draft fans of three units adopt hydraulic coupling adjustment mode. The hydraulic coupling transmits the motor energy and changes the output speed by controlling the change of momentum moment of working oil in the working chamber. The motor drives its driving wheel through the input shaft of the hydraulic coupling to accelerate the working oil, and the accelerated working oil drives the slave of the hydraulic couplingAs a turbine, the energy is transmitted to the output shaft and the load. In this way, the torque of the output shaft can be controlled by controlling the oil pressure in the working chamber to achieve the purpose of controlling the speed of the load.The speed range of the hydraulic coupling is between 20% and 95%, and its efficiency is basically proportional to the speed. With the decrease of the output speed, the efficiency is basically proportional to the decrease.The efficiency is 95% at 100% speed, 72% at 75% speed and 19% at 20% speed. The output power of the shaft of the hydraulic coupling is proportional to the third power of the speed. When the speed decreases, although the efficiency of the hydraulic coupling is proportional to the speed, the power of the motor's integrated shaft still decreases in the second power with the decrease of the speed. Therefore, when the speed is low, the output power of the fan will decreaseThe comprehensive efficiency is very low, and the energy consumption of the motor is relatively large.The design parameters of induced draft fan motor are as follows:

 

name

model

Rated power (kw)

Rated voltage (V)

Rated current (a)

Rated frequency

speed

power factor

Induced draft fan

YKKZ10-6

1800

6000

212.7

50

986

0.85

 

 

2、 Implementation plan of transformation

1Frequency converter selection and configuration scheme

According to the motor capacity of induced draft fan, the inverter hivert-y06 / 220 produced by Beijing Hekang Yisheng Frequency Conversion Technology Co., Ltd. is selected, and the rated output current is 220a.The existing induced draft fan motor and high-voltage switch are reserved. Considering the location of 6kV power distribution room, we set the spare space of dust collector power distribution room as the frequency converter room. The frequency converter cable uses the original power cable of induced draft fan, and the frequency converter to fan cable is rearranged.The control power supply of frequency converter is controlled by 380V. One way of power supply is from the transformer of frequency converter, and the other way is from the 380V system of unit. The two ways of power supply can be automatically switched without manual adjustment.The cable trench between frequency converters shall be improved on the basis of the original cable trench to ensure that it meets the construction requirements.

 

CONTACT US

VILLE INDUSTRY CO.,LTD.

Contact:Green Hsu

Mobile: 008613867838839

Email: Green@cnville.com

          Jennifer@cnville.com

Tel: 0086 574 27960025

       0086 574 27960028

Head office Add: FL 6, NO.C12 BUILDING, LANE 299 GUANGHUA RD, NINGBO R&D PARK,NINGBO HI-TECH ZONE,CHINA, 315040

Manufacture Add:NO 172 DAQING ROAD SHIPU XIANGSHAN NINGBO ZHEJIANG CHINA