Practice summary of high voltage frequency conversion transformation of shaft furnace cooling fan in Ironmaking Plant

Practice summary of high voltage frequency conversion transformation of shaft furnace cooling fan in Ironmaking Plant

1、 The necessity of energy saving of cooling fan

The cooling fan of shaft furnace is regulated by baffle (valve), a considerable amount of energy is consumed on the baffle (valve), so the potential of power saving in this aspect is very considerable.According to the analysis of the field data, there is a large margin in the operation of the equipment. Using high-voltage frequency conversion to replace the traditional fan damper and baffle adjustment has a unique advantage. While achieving substantial energy saving and consumption reduction, it can improve the speed regulation accuracy and response speed of the system, realize the soft start and soft stop of the electric machine, reduce the impact on the power grid and mechanical transmission equipment, and improve the degree of self-control,Reduce the amount of mechanical equipment maintenance, reduce the labor intensity of operators, and achieve good economic benefits for enterprises

 

2、 General situation of cooling fans before transformation (2 sets)

 

Two fans are normally open

electric machinery

Operating conditions

model

D700-13-2

model

JK134-2

Actual current

37A

Rated air volume

700m3/min

Rated power

440kW

Actual voltage

6kV

Rated pressure

28 kPa

Rated voltage

6kV

Throttle opening

Import 50%

Export 17%

Shaft power

 

Rated current

49A

Actual air volume

25000m3/h

Rated speed

2950 r/min

Rotational speed

r/min

Actual pressure

15-16 kPa

Regulation mode

Butterfly Valve

power factor

0.88

 

 

 

3、 Transformation scheme of cooling fan

6kv500kw is selected for high voltage frequency conversion, and one drive one manual bypass mode is adopted for primary circuit.The secondary control adopts remote start stop and open loop speed control in the control room.

The high-voltage inverter is installed on the East platform outside the high-voltage distribution room of the shaft furnace, and the civil engineering is separated by one span as a special independent inverter room.

 

4、 Operation of cooling fans after transformation (2 sets)

 

Two fans are normally open

electric machinery

Operating conditions

model

D700-13-2

model

JK134-2

Actual current

28A

Rated air volume

700m3/min

Rated power

440kW

Actual voltage

5kV

Rated speed

2950 r/min

Actual speed

2380r/min

Actual pressure

17kPa

Regulation mode

Frequency converter speed regulation

power factor

0.96

Actual air volume

25000m3/h

 

CONTACT US

VILLE INDUSTRY CO.,LTD.

Contact:Green Hsu

Mobile: 008613867838839

Email: Green@cnville.com

          Jennifer@cnville.com

Tel: 0086 574 27960025

       0086 574 27960028

Head office Add: FL 6, NO.C12 BUILDING, LANE 299 GUANGHUA RD, NINGBO R&D PARK,NINGBO HI-TECH ZONE,CHINA, 315040

Manufacture Add:NO 172 DAQING ROAD SHIPU XIANGSHAN NINGBO ZHEJIANG CHINA